Ultrasonic, Wired or Wireless MBUS Options, Pulse Output, RS485 Output
| 
			 Technic Features  | 
			
			 TH3-15  | 
			
			 TH3-20  | 
			
			 TH3-25  | 
			
			 TH3-32  | 
			
			 TH3-40  | 
		
|---|---|---|---|---|---|
| 
			 Pipe Size, DN (mm)  | 
			
			 DN15  | 
			
			 DN20  | 
			
			 DN25  | 
			
			 DN32  | 
			
			 DN40  | 
		
| 
			 Accuracy Class  | 
			
			 2 (EN 1434)  | 
		||||
| 
			 Environmental Classı  | 
			
			 E1 / M1 (2004/22/EC) and A (EN 1434)  | 
		||||
| 
			 Display Unit Options  | 
			
			 kWh, kW, m3, m3/h ve °C  | 
		||||
| 
			 Display Resolution  | 
			
			 Energy: 1kWh, Volume: 0,001m3, Flow: 0,001m3/h, Power: 0,1kW ve Heat: 0,1°C  | 
		||||
| 
			 Maximum Value of Thermal Power - kW (Input)  | 
			
			 235  | 
			
			 392  | 
			
			 548  | 
			
			 940  | 
			
			 1567  | 
		
| 
			 Maximum Value of Thermal Power - kW (Return)  | 
			
			 244  | 
			
			 407  | 
			
			 570  | 
			
			 977  | 
			
			 1628  | 
		
| 
			 Nominal flow rate,qp (m3/h)  | 
			
			 1.50  | 
			
			 2.50  | 
			
			 3.50  | 
			
			 6.00  | 
			
			 10.00  | 
		
| 
			 Max. Flow, qs (m3/h)  | 
			
			 3  | 
			
			 5  | 
			
			 7  | 
			
			 12  | 
			
			 20  | 
		
| 
			 Min. Flow, qi (m3/h)  | 
			
			 0.015  | 
			
			 0.025  | 
			
			 0.035  | 
			
			 0.120  | 
			
			 0.200  | 
		
| 
			 Max. flow rate (l/h)  | 
			
			 3  | 
			
			 5  | 
			
			 7  | 
			
			 12  | 
			
			 20  | 
		
| 
			 Working Pressure (PS/PN)  | 
			
			 1.6 MPa (16 bar)  | 
		||||
| 
			 Pressure Loss at qp (qp'de)  | 
			
			 25 kPa (250 mbar)  | 
		||||
| 
			 Temperature Range, Ɵ  | 
			
			 1°C .. 105°C  | 
		||||
| 
			 Limits of Temperature (Ɵmin .. Ɵmax)  | 
			
			 4°C .. 95°C  | 
		||||
| 
			 Limits of Temperature Difference (Δϴmin and Δϴmax)  | 
			
			 3K .. 70K  | 
		||||
| 
			 Heating/Cooling Switching  | 
			
			 Heating if Δϴ > + 0.2 K; Cooling if Δϴ < - 0.2 K  | 
		||||
| 
			 Mounting Orientation  | 
			
			 Horizontal ve Vertical  | 
		||||
| 
			 Battery Power Supply  | 
			
			 3.6V, C size lithium, above 10 years lifetime  | 
		||||
| 
			 Pulse Output Device Class  | 
			
			 Class OD (Item 7.1.3 of EN 1434-2:2007)  | 
		||||
| 
			 Installation Line  | 
			
			 It is preferred to install flow sensor on return pipe  | 
		||||
| Model | A | B | C | D | L | 
|---|---|---|---|---|---|
| TH315 | 130 | 108 | 81 | G 3/4” | 110 | 
| TH320 | 130 | 108 | 87 | G1” | 130 | 
| TH325 | 130 | 108 | 88 | G 11/4” | 160 | 
| TH332 | 130 | 108 | 91 | G 11/2” | 180 | 
| TH340 | 130 | 108 | 94 | G2” | 200 | 

